Include joist self weight in design report

Since Forte does not add the joist self weight, the joist self weight for selected product should be presented in the report so that the designer can double check their design dead load. Alternately, add a setting to specify that dead loads are superimposed and do not include joist self weight.

  • Guest
  • Mar 24 2020
  • Functionality Exists
  • Attach files
  • Guest commented
    April 04, 2020 00:07

    You're overthinking this, it's perfect the way it is right now. For TJI/LSL floors, just put your floor dead at 12 PSF and you're good unless you have stone/marble/tile floors or heavy countertops on it. The 12# covers drywall, framing, insulation, floor covering, etc.

  • Guest commented
    March 26, 2020 21:05

    Hi

    dead load for repetitive joist design is assumed as user input under the dead load. Only beam design is it added by program as separate dead load and listed in Report . A report note would sure help...but it is in the Help Menu